AIMS Data Center
Our global partner AIMS is Malaysia and South East Asia’sleading carrier neutral data centre operator and managed services provider. They provide international class data storage and ancillary services, augmented by an unrivaled platform for interconnectivity. AIMS has the most densely populated communications facility in South East Asia. All domestic telcos and more than 50% foreign carriers are hosted in their data centre. They have over 80% of Malaysia's active service providers residing with them. AIMS data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.



Building Floor Information
Floor Height:3.8 meter, slab to slab
Floor Load:5 k-N per square meter
Command Centre &Security Department: Command Centre is located at Ground floor.
Two levels of security control:
1st level : access to the building compound
2nd level: access to the data centre




Building Information
Building Information:Single block 18-storey commercial building and 3 basement parking.The building consists of 7-storey data centre floors and 3 sub-floor for the installation of mechanical and electrical facilities and power plants.
Power Supplies:11kV HT power feed from TNB power grid
Power Capacity:5 MVA




Data Centre Specification
Critical Load Power Density:100 watts per square feet
Cooling Density:120 watts per square feet
Cabinet Dimension:42RU 600mm (width) x 1000mm (depth)
Space Configuration
- Cold Aisle Spacing:1,200mm
- Hot Aisle Spacing:1,000mm


Raised Floor System
Gross Raised Floor Area per Floor:6,500 square feet
Usable Raised Floor Area:5,000 square feet
Concentrated Load:4.5 kN
Uniform Load:12 K-N per square meter


Uninterruptible Power Supply (UPS) System
UPS System: True-online Double Conversion Static UPS
DRUPS is installed to protect data centre critical loads
Static UPS Capacity:1200kVA and 800kVA
Total Static UPS Capacity:2 x 2000kVA
UPS Battery Autonomy:10 minutes at full load
DRUPS Capacity:1100kVA


Power Distribution Unit (PDU)
Isolation Transformer:K-13/K-20 Rated Isolation Transformer is included in each PDU
PDU Capacity:200kVA/225kVA
AC Voltage at Cabinet Level:240V/ 50 Hz ,415V/50 Hz


Cooling
Chiller System: Air cooled, chilled water based ACMV system water is installed
Chiller Redundancy:N+1 redundancy for chiller unit
Temperature Control:22 Degree +/- 2º
Humidity Control:50 RH +/- 10 RH


 